Summary : Choosing between riser and plenum cables is critical for both fire safety and code compliance. Riser cables suit vertical shafts without airflow, while plenum cables are required in air-handling spaces like ceiling voids. This guide clarifies when to use each type, emphasizing safety, inspection standards, and long-term cost implications for structured cabling installations.
In structured cabling, performance is not the only consideration. Safety is, as well—and it’s absolute. Whether installing a new office network, retrofitting a warehouse facility, or constructing a data center, cable selection makes all the difference in signal integrity and compliance with fire safety codes that protect people, property, and uptime.
One of the most ill-understood—but essential—cable installation choices is whether to use riser-rated or plenum-rated cable. An incorrect decision can result in failed inspections, rework, and severe liability if a fire occurs.
This guide dispels the uncertainty. When you’ve asked yourself, “Do I need plenum cables here, or will riser do?” we’ll take you step-by-step through the definitive criteria so you can make the correct decision. We’ll divide it by building areas, compliance with local codes, and material-level fire safety, so you can decide wisely and safely.
Let’s start with riser spaces—what they are and why they matter in this discussion.
A riser is any vertical space within a building connecting multiple floors. Think elevator shafts, stairwells, mechanical chases, and conduit paths running from one floor to the next. These are the arteries that carry infrastructure, like water pipes, electrical conduits, and yes, network cables between levels.
What makes riser spaces unique is that they don’t handle air circulation. In other words, if there’s a fire on one floor, the chances of smoke being pulled through a riser by an HVAC system are very low. There may still be fire risk, but the spread of smoke through ventilation is not a primary concern.
Now that you understand the space, let’s talk about the cable.
Riser-rated cables are specifically designed for those vertical runs between floors. Technically known as CMR (Communications Riser), these cables are tested under UL 1666, which measures flame propagation within vertical shafts.
Key features of riser cabling include:
You’ll often find riser-rated cabling used in:
You can’t use riser cables in spaces where air is actively circulated. That’s where plenum cables come in.
Plenum spaces are often hidden in plain sight. The most common example? The area above your drop ceiling.
In many commercial buildings, the HVAC system uses the ceiling void—or sometimes the floor void—for air return. These plenum spaces allow conditioned air to circulate to the heating or cooling units. But here’s the risk: in a fire, these areas can rapidly move smoke and flames from one part of the building to another.
That’s why plenum spaces are tightly regulated in building and fire codes. Any cable installed in a plenum space must meet much more stringent fire resistance and smoke toxicity standards.
Plenum-rated cables, marked as CMP (Communications Plenum), are engineered for those air-handling zones where smoke can quickly travel. These cables meet strict standards defined by NFPA 90A and NEC Article 800, both of which require cable jackets that:
The jacket materials used in plenum cables are often made from FEP (fluorinated ethylene propylene), PTFE (Teflon), or low-smoke PVC blends—substances that burn less aggressively and produce less harmful fumes.
You’ll see plenum-rated cables in:
In essence, any time the cable runs through an air-carrying duct or ceiling, it must be plenum-rated.
Here’s a side-by-side breakdown of the two cable types for quick reference:
Property | Riser (CMR) | Plenum (CMP) |
Fire Rating | UL 1666 | NFPA 90A, UL 910 |
Jacket Material | PVC | FEP, PTFE, Low-smoke PVC |
Smoke/Toxicity | Higher | Lower |
Use Case | Vertical shafts without airflow | Air-handling spaces like ceilings |
Can it Be Used In a Riser? | Yes | Yes |
Can it Be Used In a Plenum? | No | Yes |
Cost | Lower | Higher |
A simple rule of thumb: Plenum cables can always be used in riser spaces, but riser cables can never be used in plenum areas.
The cabling world is full of acronyms. Here are the ones that matter most in this context:
Knowing which cable to use boils down to this: where is it going, and how is air handled in that space?
Default to plenum. Yes, it’s more expensive—but it covers both plenum and riser zones, removes ambiguity, and satisfies the toughest inspections.
This isn’t just about ticking a box. Using the wrong cable in the wrong zone can lead to:
Cables don’t just carry data—they’re part of your building’s fire containment strategy. That’s why both plenum and riser ratings exist, and why they’re defined by national codes like the NEC and local AHJs (Authorities Having Jurisdiction).
It’s not a gray area. It’s black and white.
It’s tempting to save money on cabling, especially when looking at thousands of feet of cable across multiple floors. However, cost-cutting on the wrong cable type can cost more in the long run.
So ask yourself: is a few hundred dollars of savings worth the risk of non-compliance or failed occupancy?
Network Drops has been working in structured cabling since 1986. Our technicians don’t just pull cable—they bring decades of code knowledge, safety-first installation practices, and hands-on experience in everything from office risers to complex HVAC plenum zones.
We don’t guess. We don’t cut corners. And we don’t leave our clients hanging when the inspector shows up.
Whether it’s a small office upgrade or a large-scale infrastructure build-out, we help you pick the right cable for the right space and ensure it’s done right the first time.
Choosing between riser and plenum cables isn’t just a question of budget or technical specs—it’s a matter of building safety and legal compliance. It’s about protecting people, meeting standards, and installing a network that’s not just fast and stable, but fire-resistant and future-proof.
If you’re planning a network project and aren’t 100% sure what cable your space requires, don’t guess. Reach out to a certified, code-savvy installer at Network Drops. It’ll save you time, money, and risk, and might save lives.
Need help mapping out your cabling plan? Let’s walk the site together.
No. Even if riser cables are inside conduit or enclosed, they still do not meet the strict fire and smoke standards required in plenum spaces. Most inspectors won’t approve it, and you could violate the code. Always use plenum-rated cables in any area used for air circulation.
It’s a code violation—and a serious one. You could fail inspection, delay occupancy, face rework costs, or even void insurance coverage in the event of a fire. More importantly, you’re increasing the risk to life safety in air-handling spaces. It’s not worth the shortcut.
Yes. Plenum-rated cables exceed the fire resistance of riser-rated ones and are fully approved for vertical shaft use. Plenum cables are the safer, more versatile option to simplify ordering or ensure you’re always compliant.
If the area is used for return air—typically above drop ceilings or under raised floors—it’s likely a plenum. You’ll often find these connected to HVAC systems. Consult your building’s mechanical plans or a licensed installer when in doubt. It’s better to verify than assume.
The materials used in plenum jackets—like FEP or low-smoke compounds—are more expensive to produce and test. They’re engineered to resist fire spread and emit less toxic smoke. The higher price reflects the stricter safety standards they’re built to meet.
"*" indicates required fields
Scott Fcasni is the driving force behind Magna5’s commercial datacomm cabling division, delivering expert solutions that power reliable, high-performance network infrastructures. With extensive experience in structured cabling and a commitment to precision, Scott ensures that every project—whether for small businesses or large enterprises—meets the highest standards of quality and scalability.